We performed an environmental monitoring in an hospital to estimate the level of contamination from Legionella spp., in connection with several treatments of reclamation. In period 2002-2006 we executed 238 samplings in 21 units hospitals (from hot water, biofilm, filter of the conditioning system, instrument for the assisted respiration) for the detection of Legionella spp. The contaminated points have been subordinates to reclamation (hyperchlorination, maintenance of boilers/tanks, taps' and showers' substitution, increased temperature, elimination of dead points of the system and chlorine dioxide) and subsequently we sampled to verify the efficiency of the disinfection. Environmental investigation found 58% of the cases positive for Legionella spp. (139/238), with maximum count in order of the 10(4) UFC/L, demonstrating colonization of Legionella pneumophila (132/139, 70% Serogroup 2-14, 19% Serogroup 1, 11% both). The used treatments were effective, in different ways, in the short period, but not in the medium-term, because progressive recolonization happened approximately after a month; only the use of chlorine dioxide brought to counts less than 100 UFC/L until now. Chlorine dioxide seems to maintain a mainly protecting effect, however this effectiveness will have to be demonstrated also for longer periods.

Sorveglianza ambientale di Legionella pneumophila e metodi di bonifica a confronto in strutture sanitarie di Milano (risultati di un quinquennio) / M.G. Galli, M. Tesauro, A. Bianchi, F. Pregliasco, M. Consonni. - In: ANNALI DI IGIENE MEDICINA PREVENTIVA E DI COMUNITÀ. - ISSN 1120-9135. - 19:6(2007), pp. 533-540.

Sorveglianza ambientale di Legionella pneumophila e metodi di bonifica a confronto in strutture sanitarie di Milano (risultati di un quinquennio)

M.G. Galli
Primo
;
M. Tesauro
Secondo
;
A. Bianchi;F. Pregliasco
Penultimo
;
M. Consonni
Ultimo
2007

Abstract

We performed an environmental monitoring in an hospital to estimate the level of contamination from Legionella spp., in connection with several treatments of reclamation. In period 2002-2006 we executed 238 samplings in 21 units hospitals (from hot water, biofilm, filter of the conditioning system, instrument for the assisted respiration) for the detection of Legionella spp. The contaminated points have been subordinates to reclamation (hyperchlorination, maintenance of boilers/tanks, taps' and showers' substitution, increased temperature, elimination of dead points of the system and chlorine dioxide) and subsequently we sampled to verify the efficiency of the disinfection. Environmental investigation found 58% of the cases positive for Legionella spp. (139/238), with maximum count in order of the 10(4) UFC/L, demonstrating colonization of Legionella pneumophila (132/139, 70% Serogroup 2-14, 19% Serogroup 1, 11% both). The used treatments were effective, in different ways, in the short period, but not in the medium-term, because progressive recolonization happened approximately after a month; only the use of chlorine dioxide brought to counts less than 100 UFC/L until now. Chlorine dioxide seems to maintain a mainly protecting effect, however this effectiveness will have to be demonstrated also for longer periods.
Settore MED/42 - Igiene Generale e Applicata
2007
Article (author)
File in questo prodotto:
Non ci sono file associati a questo prodotto.
Pubblicazioni consigliate

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/2434/41329
Citazioni
  • ???jsp.display-item.citation.pmc??? 0
  • Scopus 5
  • ???jsp.display-item.citation.isi??? ND
social impact